LS10143-001SK-E Programming
9-26
A screen similar to the one shown in Figure 9-12 will display.
Figure 9-12 Changing Day/Night Sensitivity Time
9.6.3 Holiday Days
Up to 18 dates can be designated as holidays. When day/night sensitivity is enabled, all photoelectric smoke
detectors in the system will use night sensitivity for the entire day on days designated as holidays.
To add or change a holiday, follow these steps:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select 7 for Panel Programming.
3. Select 5 for System Options.
4. Select 3 for Holiday Days. A screen similar to that shown in Figure 9-13 will display.
5. Edit the holiday schedules you wish to change or add holidays as needed in the programmable holiday loca-
tions.
Figure 9-13 Edit Holidays Screen
6. Enter the month of the holiday, then press ENTER. Enter the day of the month for the holiday, then press
ENTER.
7. Repeat steps 6 for any remaining holidays you wish to program.
9.6.4 Time Options
Through this programming option you can set the water flow delay time, alarm verification time, AC report
delay, AC-Frequency, Auto-Resound, and Clock Format.
9.6.4.1 Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a water flow
switch. The delay is system-wide. All water flow switches on the system will use the same delay period.
To access the screen for programming water flow delay, follow these steps:
Pre-programed
holidays
Programmable
holiday locations