Serial essernet
®
interface (SEI1)
FB 798819 / 05.18 43
7.4.3 SEI1 EDP, bidirectional (Part No. 784856) - VAS
Connection of a VARIODYN
®
D1 voice alarm system to ESSER fire alarm control panels via
the SEI1.
7
1
2
3
4
PA1
PA2
essernet
®
max. 10 m
DOM
5
6
Fig. 2: Wiring principleSEI1 (Part No. 784856) to a voice alarm system (VAS)
ESSER fire alarm control panel (FACP)
Serial essernet
®
Interface (SEI1)
TWI-RS232 adapter (Part No. 583386.21) – see Chapter 10.5
Loudspeaker
Call stations
Digital Output Module (DOM)
Power amplifier (PA)
Performance features
The VARIODYN
®
D1 system can be controlled by the fire alarm control panel via this
connection.
Collective faults of the VARIODYN
®
D1 system are reported to the FACP.
The connection between the two systems is constantly monitored for short-circuit and
interruption.
The system time and the date of both systems are automatically synchronised (received
from FACP DOM or DOM FACP – depending on the selection).
Activation via control zones
The activation is carried out via control zones within the essernet
®
, in order to transmit the
information for the activation of an alarm circuit to the DOM. For this purpose, corresponding
activations of control zone outputs are achieved via zone inputs and are sent via the SEI1 to the
DOM in the ESSER FACP.
The 'Control zone activated/triggered' status is assessed by the DOM.