Serial essernet
®
interface (SEI1)
FB 798819 / 05.18 45
Note on the essernet
address
In sub net, e.g. a serial essernet
®
interface (SEI1) and one FACP, only the essernet
®
address
No. 1+2 should be configured. The essernet
®
address always starts with no. "1" with a further
increase. All other configurations are impossible.
The essernet address for the SEI1 in the main network is freely selectable, but it is meaningful
to select the upper next free essernet
®
address for this SEI1.
Operation from the sub net into the main network is not possible.
This application is not suited to build a remote operating panel for the main
network based on the FACP 8000 / IQ8Control-Remote unit.
Faults from the sub net are also displayed on the fire alarm control panels in
the main net.
Example display
Fault in sub net – FACP No. 01 with message 13
Display in the main network – fault on primary loop 0113 in the sub net.