FMC2000 User’s Guide
delayed on or delayed off, plus logic can be programmed so that
relays only open (or close) when specific multiple monitors go
into alarm simultaneously (AND) or when one or more of a
specific set of monitors goes into alarm.
Enter programming by pressing ENTER. Step from one column to
the next by using the up and down arrows.
16.2 Type
This enables each relay to be set as Low, High, or Fault. The relay
is only triggered when that specifically programmed type of alarm
state occurs.
1. Press Enter. You will see a menu of L, H, F, with the
instrument number before it.
2. Press the up or down arrow to select L, H, or F.
3. Press Enter to save the new value.
4. Press the up or down arrow to step to the next or previous
column.
16.3 DON
Delay On. This is the delay time for the relay switch being
activated.
1. Press Enter.
2. Press number keys to enter a new Delay On value (0 to 60
seconds).
3. Press Enter to save the new value.
4. Press the up or down arrow to step to the next or previous
column.