EasyManua.ls Logo

Honeywell MPA2C3 - Page 106

Honeywell MPA2C3
183 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
100 MPA2C3 Installation Guide
RS485 Bus Termination.
An RS485 bus must be terminated with a resistor at both ends of the RS-485 bus.
If the MPA2C3 panel is at the beginning or end of the I/O Devices RS485 bus, then
the bus must be closed with 120 Ohm resistor. On Dipswitch SW3 both bit 5 and 6
(EOL I/O DEV) must be set to ON position to add the resistor to the RJ45 I/O
DEVICES RS485 communication wires.
Setting DIP Switches and Jumpers
The access control panel involves 3 DIP Switches and 14 jumpers. The switches are
used to configure the IP addresses, to configure the panel for different reader con-
nections, to configure primary panel and so forth. The jumpers are used for Door
output power source selection and relay contact type (2 per door), for reader wie-
gand/OSDP selectio"Wiegand Reader Wiring" on page 3-52 for FACP bypass
(see".FACP Jumper" on page 3-106) and for Back tamper bypass ("T-Back
Jumper" on page 3-106).
DIP Switch 3 (SW3)
OFF
12345678
ON
Set
1-4 OFF
5 EoL RS485 bus I/O Devices
6 EoL RS485 bus I/O Devices
7 EoL RS485 bus Downstream Panels
8 EoL RS485 bus Downstream Panels
Set
DIP Switch 1 (SW1)
OFF
12345678910
ON
1Wiegand READER 1(A/B)-OSDP1
2 OFF
3 secondary /Primary panel(ON)
4 User IP address /Deafault IP address
5 Address 5
6 Address 4
7 Address 3
8 Address 2
9 Address 1(ON)
10 Wiegand READER 2(A/B)-OSDP2
Set
DIP Switch 2 (SW2)
OFF
1234
ON
1 EoL OSDP1
2 EoL OSDP1
3 EoL OSDP2
4 EoL OSDP2
Wiegand Reader
OSDP Reader

Table of Contents

Other manuals for Honeywell MPA2C3

Related product manuals