AM-1224  Installation and programming manual  PAGINA -  39 
AM-1224_manu  Doc. M-124.1-AM1224-ENG Rev A.1  NOTIFIER ITALIA
 
  TIM 
Is the user that allow to programm the output activations with periodical time limits. 
 
 There are two possible formats: 
 
 
 
 
FORMAT Type 1 : TIM (SU MO TU WE TR FR SA     00.MM          00.MM) 
     
 
 
 
    
Where : 00 = hours, MM = minutes 
This format give the possibility to programm weekly limits, for fixed days of the week.   
 
 
 
 
FORMAT Type 2 :  TIM  (MM   GG   AA           OO.MM       OO.MM) 
 
 
 
 
 
Where: MM = month, GG = day, AA =year 
This format give the possibility to programm annual limits. 
 
Example: IF the equation of output 02 is: TIM (SA SU 07.30 13.59) 
THEN the output 02 will be active saturday and sunday from 07.30 AM to 13:59. 
 
 
NOTE: 
 
  If the day, month or year is not indicated, the value takes up the “EACH” meaning. 
Introduce two signs do not specify anything  “  “ see example below: 
 
 TIM (   07.30 13.59) 
 
  The values of start time and end time, use the 24-hour format (midnight = 00.00 ... 23.59) 
 
 
  the “00.MM” value as end time has to be greater than the start time. 
 
  the maximum value for start time and end time is 23:59 
 
 
Days of activation   
      (optional)       
 
Start time  End time
Enter a space 
characte
Enter a space 
characte
Days of activation   
      (optional)   
Start time  End time
Enter a space 
characte
Enter a space 
characte