PAGINA - 6 Installation and programming manual AM-1224
NOTIFIER ITALIA Doc. M-124.1-AM1224-ENG Rev A.1 AM-1224_manu
C
C
h
h
a
a
r
r
a
a
c
c
t
t
e
e
r
r
i
i
s
s
t
t
i
i
c
c
s
s
o
o
f
f
r
r
e
e
l
l
a
a
y
y
o
o
u
u
t
t
p
p
u
u
t
t
s
s
EN54
!
EN54-2 7.7
Alarm Output
The General Alarm relay is a free voltage contacts output.
Note : To comply the EN 54.2. 7.7 don’t connect on this output remote warning
devices (as in example a telephone dialer) because the connection is not
supervised
F
F
U
U
S
S
E
E
L
L
I
I
S
S
T
T
Name Description Electrical Features
F1 User output fuse Fast glass F1AL
F2 Sounder output fuse Fast glass F1AL
F3 Battery output fuse Resettable Fuse MFR250
F4 Mains (230Vac ) Fuse Fast glass F1AL
L
L
i
i
n
n
e
e
s
s
c
c
o
o
n
n
n
n
e
e
c
c
t
t
i
i
o
o
n
n
s
s
:
:
EN54
!
EN54-2 8.8
Fault Output
The general Fault relay is normally energized.
In Fault condition it will be de-energized.
Note: To comply the EN 54.2.7.7 don’t connect on this output remote warning
devices (as in example a telephone dialer) because the connection is not
supervised.
Detector
800 SERIES or ECO1000 SERIES
FUNCTION
General Alarm
General Fault
Feature
Max 2A resistive 30Vdc, NO-NC programmable by Jumper JALL
Max 2A resistive 30Vdc, NO-NC programmable by Jumper JGST
N. O. Call Point contact
2K7
1/4W
1K
1/4W

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier AM12-24 and is the answer not in the manual?

Honeywell Notifier AM12-24 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier AM12-24
CategoryFire Alarms
LanguageEnglish

Related product manuals