FireWarden 100-2/E — P/N 52778:A 11/04/2005 105
Master Programming Level Programming
3+1, 4+1 Express and 4+1 Standard
The information shown in Table 3.2 is automatically programmed for the Central Station phone
number Event Codes when any of these Formats are selected. Enter 0 for an Event Code Setting to
disable the report.
Table 3.2 Event Codes
Event Description Event Code Settings
Active Restoral
PULL STATION 1 E
MON-USER-DEF-1 1 E
WATERFLOW 1 E
MON-USER-DEF-2 1 E
SMOKE (PHOTO) 1 E
DET-USER-DEF-1 1 E
SMOKE (ION) 1 E
DET-USER-DEF-2 1 E
HEAT DETECT 1 E
DET-USER-DEF-3 1 E
SMOKE DUCT-P 1 E
DET-USER-DEF-4 1 E
PHOTO W/HEAT 1 E
DET-USER-DEF-5 1 E
DUCT SUPERVISORY 8 E
DET-USER-DEF-6 8 E
PHOTO SUPERV 8 E
DET-USER-DEF-7 8 E
not used 0 0
not used 0 0
not used 0 0
not used 0 0
MONITOR 1 E
MON-USER-DEF-3 1 E
not used 0 0
not used 0 0
SMOKE CONVEN 1 E
MON-USER-DEF-5 1 E
HEAT CONVEN 1 E
MON-USER-DEF-6 1 E
MEDIC ALERT 0 0
MON-USER-DEF-7 0 0
HAZARD ALERT 0 0
MON-USER-DEF-8 0 0
TORNADO ALRT 0 0
MON-USER-DEF-9 0 0
not used 0 0
not used 0 0
TAMPER 8 E
MON-USER-DEF-11 8 E
MON SUPERVISORY 8 E
MON-USER-DEF-12 8 E
MON SUPERV AUTO 8 E
MON-USER-DEF-13 8 E
POWER MON 6 A
MON-USER-DEF-14 6 A
TROUBLE MON POINT_FAULT code will always be transmitted
MON-USER-DEF-15 POINT_FAULT code will always be transmitted
PROCESS MON 0 0
MON-USER-DEF-16 0 0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER FireWarden-100-2 and is the answer not in the manual?

Honeywell NOTIFIER FireWarden-100-2 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER FireWarden-100-2
CategoryFire Alarms
LanguageEnglish

Related product manuals