EasyManua.ls Logo

Honeywell NOTIFIER FireWarden-100-2 - Page 109

Honeywell NOTIFIER FireWarden-100-2
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FireWarden 100-2/E — P/N 52778:A 11/04/2005 109
Master Programming Level Programming
Ademco Contact ID Format
The information shown in Table 3.4 is automatically programmed for the Central Station phone
number Event Codes when Ademco Contact ID Format is selected. Enter 000 for an Event Code
Setting to disable the report.
Table 3.4 Event Codes
Event Description Event Code Settings
Active
PULL STATION 115
MON-USER-DEF-1 115
WATERFLOW 113
MON-USER-DEF-2 113
SMOKE (PHOTO) 111
DET-USER-DEF-1 111
SMOKE (ION) 111
DET-USER-DEF-2 111
HEAT DETECT 114
DET-USER-DEF-3 114
SMOKE DUCT-P 116
DET-USER-DEF-4 116
PHOTO W/HEAT 111
DET-USER-DEF-5 111
DUCT SUPERVISORY 200
DET-USER-DEF-6 200
PHOTO SUPERV 200
DET-USER-DEF-7 200
not used 000
not used 000
not used 000
not used 000
MONITOR 110
MON-USER-DEF-3 110
not used 000
not used 000
SMOKE CONVEN 111
MON-USER-DEF-5 111
HEAT CONVEN 114
MON-USER-DEF-6 114
MEDIC ALERT 100
MON-USER-DEF-7 100
HAZARD ALERT 150
MON-USER-DEF-8 150
TORNADO ALRT 150
MON-USER-DEF-9 150
not used 000
not used 000
TAMPER 144
MON-USER-DEF-11 144
MON SUPERVISORY 200
MON-USER-DEF-12 200
MON SUPERV AUTO 200
MON-USER-DEF-13 200
POWER MON 330
MON-USER-DEF-14 330
TROUBLE MON POINT_FAULT code will always be transmitted
MON-USER-DEF-15 POINT_FAULT code will always be transmitted
PROCESS MON 000
MON-USER-DEF-16 000