18 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021
Introduction LED Operation
AFP-100
AIM-200
Monitor Module
Control Module
Detector
Blinks RED
Blinks GREEN
Blinks RED
RED continuous
Blinks GREEN
RED continuous
N/A
N/A
N/A
N/A
N/A
N/A
AFP-200 Monitor Module
Control Module
Detector
Blinks RED
Blinks GREEN
Blinks RED
RED continuous
OFF
RED continuous
N/A
N/A
N/A
N/A
N/A
N/A
N16, NFS-320,
NFS2-640,
NFS-640
NFS2-3030,
NFS-3030
Monitor Module
Control Module
Detector
Blinks RED
Blinks GREEN
Blinks RED
RED continuous
GREEN continuous
RED continuous
Blinks GREEN
Blinks GREEN
Blinks GREEN
RED continuous
GREEN continuous
RED continuous
CLIP Mode FlashScan® Mode
Table 1.4 LED Operations
NOTE: In CLIP mode, the LPX-751 and HPX-751 blink GREEN in standby and stay RED when activated.