EasyManuals Logo

Honeywell NOTIFIER SLC User Manual

Honeywell NOTIFIER SLC
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
40 Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021
Monitor Modules NFPA Class A IDC Using Monitor Modules
6.4 NFPA Class A IDC Using Monitor Modules
Connect the SLC wiring to the module terminals 1 (–) and 2 (+).
Each FMM-1 module takes one address on the SLC. Use the rotary switches on the module to set it to the required SLC address.
Figure 6.7 shows typical wiring for a supervised and power-limited NFPA Class A IDC using the FMM-1 module.
Module installation notes:
1. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps @ 24 VDC (nominal).
See Appendix A, “Power Considerations”, on page 66 for information on monitoring 24 VDC power.
2. The IDC provides the following services (do not mix):
Fire alarm service
Automatic and manual waterflow alarm service with normally open contact devices
Sprinkler supervisory service with normally open contact devices
Security service
3. Refer to the Device Compatibility Document for compatible smoke detectors.
47K ELR
(supplied
with module)
Heat
detector
SLC
FMM-1
IDC
24 VDC Power
Filtered, Regulated,
Resettable
24 VDC
Four-wire
Detector Base
Manual pull
station
From Supply
To Next IDC
or
Supervision Device
SLC-idcB1tpH.wmf
Figure 6.6 Typical Class B IDC Wiring with FMM-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SLC and is the answer not in the manual?

Honeywell NOTIFIER SLC Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SLC
CategoryControl Panel
LanguageEnglish

Related product manuals