EasyManuals Logo

Honeywell NOTIFIER SLC User Manual

Honeywell NOTIFIER SLC
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021 45
Wiring a Class B NAC (Two-Wire) with Addressable Control Modules Control Modules
7.2.1 Wiring a Solenoid with the FCM-1-REL
(For use with NFS2-3030, NFS2-640, NFS-320(C), and NFS-320SYS.) Figure 7.3 shows the connections to wire the FCM-1-REL to a
solenoid. For UL 864 10th edition applications requiring a manual disconnect switch on the releasing device, see Section 7.5, “Connect-
ing a Releasing Device to the Addressable Control Module”.
7.3 Wiring a Class B NAC (Two-Wire) with Addressable Control Modules
Figure 7.4 depicts a supervised and power-limited NFPA Class B Notification Appliance Circuit (NAC) using the FCM-1 module. In the
sample wiring drawing below, polarized alarm notification appliances are shown connected to the module in a two-wire configuration.
1. See Appendix A, “Power Considerations”, on page 66 for information on monitoring 24 VDC power.
2. Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and
horns).
3. A power supervision relay is required only on the last module of the power run unless:
using the no-relay alternative wire method; see Figure A.2, “Alternate: 2-Address Method of Supervising a 24 VDC Circuit -
Class B”.
using a panel with FlashScan type IDs that provide built-in power supervision. Refer to the panel’s installation documentation
for a list of type codes.
4. Do not T-tap or branch a Class B circuit.
5. Terminate the circuit across the last device using a UL-listed End-of-Line Resistor 47K, 1/2-watt, SSD P/N A2143-00 (ELR-47K in
Canada).
6. Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each
device.
J1
Figure 7.3 FCM-1-REL Wiring Locations and Rear View - Jumper Location
SLC (-)
SLC (+)
24 VDC (-)
24 VDC (+)
Solenoid A (-)
Solenoid A (+)
Solenoid B/A (+)
Solenoid B/A (-)
FCM-1-REL
Wiring Connections
When using the
FCM-1-REL for
Class B
applications,
remove jumper J1.
FCM-1-REL
Rear View - Jumper Location
f
c
m
-
1
-
r
e
l
.
w
m
f
,
f
c
m
-
1
-
r
e
l
_
b
a
c
k
.
w
m
f
NOTE: FlashScan mode only: The FCM-1-REL will not function on an SLC loop that is programmed for CLIP mode.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SLC and is the answer not in the manual?

Honeywell NOTIFIER SLC Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SLC
CategoryControl Panel
LanguageEnglish

Related product manuals