Notifier SLC Wiring Manual — P/N 51253:U9 12/3/2021 9
Reference Documentation Introduction
Installations of UL 864 10th Edition certified equipment are permitted to use UL864 9th Edition certified equipment when
approved by the local Authority Having Jurisdiction (AHJ).
For product compliance, refer to the UL/ULC listing cards located on the UL online certification directory.
https://iq.ulprospector.com/en/
The following products have not received UL 864 9th or 10th Edition certification and may only be used in retrofit applications.
Operation with products not tested for UL 864 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest
edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ).
Wiring class designations changed between UL 9th and 10th edition to reflect changes in NFPA 72 descriptions. The changes are sum-
marized here for users who are more familiar with the older descriptions.
1.3 Reference Documentation
The table below provides a list of documents referenced in this manual, as well as documents for selected other compatible devices. The
document series chart (DOC-NOT) provides the current document revision. A copy of this document is included in every shipment. See
Appendix E, “Canadian Versions of SLC Devices” for Canadian part numbers. Only N16 supports self-test devices. Current release of
N16 is for UL applications.
ACPS-2406
•AFP-100
•AFP-200
AFP-300/AFP-400
AIM-200
AM2020/AFP1010
•CMX-1
•CMX-2
FCPS-24/E
LIB-400
•MMX-1
•MMX-101
•MMX-2
MPS-24A/E
MPS-24B/E
MPS-400
•NCA
NFS-3030 with CPU-3030
NFS-640 with CPU-640
System 5000
XP Series (XPP-1, XPC-8, XPM-8 &
XPR-8)
•XP5-C
•XP5-M
Old Designations
New
Designations
IDC NAC SLC Smoke Control
Releasing
Devices
Supplementary
Style B and C
(Class B)
Style Y (Class B) Style 4 (Class B) Class B
Style D and E
(Class)
Style Z (Class A) Style 6 (Class A) Class A
Style 7 (Class A) Class X
End to end
verification
Class C
Fail safe Class D
Non-supervised Class E
Table 1.1 Wiring Designations - History of Changes
Document Number
Compatible Conventional Devices (Non-addressable)
Device Compatibility Document 15378
Fire Alarm Control Panel (FACP) and Main Power Supply Installation
AFP-100 Instruction Manual 51010
AFP-200 Instruction Manual 15511
AFP-300/AFP-400 Installation, Operations, and Programming Manuals 50253, 50259, 50260
System 5000 with AIM-200: Refer to the AIM-200 Manual 15949
System 5000 Installation, Operations, and Programming Manuals 15583, 15581, 15584
AM2020/AFP1010 Installation Manual 15088
NFS-640 Installation, Operations, and Programming Manuals 51332, 51334, 51333
NFS-3030 FACP Installation, Operations, and Programming Manuals 51330, 51345, 51344
NFS-320 and NFS-320SYS UL Listing Document 52745LD
NFS2-640 UL Listing Document 52741LD
NFS2-3030 UL Listing Document LS10006-051NF-E
N16 Inspire Series UL Listing Document LS10234-051NF-E
SLM-318 Installation Document LS10243-000NF-E
FireWarden SLC Wiring Manual (Use this manual for Notifier FireWarden series equipment 52304
Voice Alarm System Manual 51252
FireVoice-25/50 & FireVoice-25/50ZS Manual 52290
Table 1.2 Reference Documentation (1 of 4)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER SLC and is the answer not in the manual?

Honeywell NOTIFIER SLC Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER SLC
CategoryControl Panel
LanguageEnglish

Related product manuals