6820 / 6820EVS Manual P/N LS10144-001SK-E:C  09/28/2017 99
8.2.2  Output Circuit Mapping
Figure 8.3 is a simple example showing how to assign notification and relay output circuits to groups. For an example of a simple floor 
above/floor below application, see Figure 8.5.
Figure 8.3  Example of Assigning Output Circuits to Groups
8.2.3  Event Mapping 
There are 11 types of Zone events 14 types of Panel events, and 6 types of Site events that can be mapped (see Table 8.1). For each event 
type, you can activate output groups and patterns. Mapping examples are shown in Figure 8.4, Figure 8.5 & Figure 8.6.
System Zone Panel Site
Fire
Manual Pull Alarm System Aux 1 Alarm Fire Drill
Water Flow Alarm System Aux 2 Alarm General Fire Alarm
Detector Alarm 
(heat or smoke detectors)
General Fire Supervisory
Zone Aux 1 Alarm  General Fire Pre-Alarm
Zone Aux 2 Alarm
Interlock Alert
Interlock Release
Pre-Alarm
Fire Supervisory
Status Point
CO Alarm
CO Supervisory
Emergency
LOC EVS 1-8 Alarm
General EVS Alarm
General EVS Supervisory
Point EVS 1-8 Alarm
Table 8.1  : Event Types