6820 / 6820EVS Manual P/N LS10144-001SK-E:C  09/28/2017 125
10. Repeat steps 1 through 9 for all circuits.
9.5.4  Point Programming For 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W and 
EVS-CE4 Modules
To program 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W, or EVS-CE4 module points:
1. Enter the installer code. The panel will automatically go to the main menu.
2. Select 7 for Program Menu.
3. Press 4 to enter point menu.
Choices Type Selections
Function Selections 
for each Type
Comments
Enter Point
Select Type UNUSED
B NOTIF NOTIF Output
Control Circuit
A NOTIF
AUX_PWR CONSTANT Constant auxiliary power.
AUX RESET Resettable auxiliary power.
AUX DOOR Door holder auxiliary power.
Aux SYNC Aux Power for System Sensor
B SWITCH MANUAL PULL Refer to comments column of
Table 9.3 for description of these options.
Latch or Non-latching feature only appears for 
WATERFLOW, FIRE SUPERVISORY, FIRE 
TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM 
AUX1, SYSTEM AUX2, EVS INPUT, EVS TAMPER, 
and EVS SUPERVISORY.
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
EVS INPUT User also has EVS Event Number 1-8 option for 
EVS INPUT. Only available when an EVS-VCM is 
installed in the system.
EVS TAMPER
EVS SUPERVISORY
A SWITCH Same as B SWITCH
B DETECT 2-WIRE SMOKE Used for Class B, 2-wire detectors.
4-WIRE SMOKE Used for Class B, 4-wire detectors.
CO 4-WIRE DET Used for Class B, 4-wire CO detectors.
CO 4-WIRE SUP DET Latching or Non-latching used for Class B, 4-wire 
CO Supervisory detectors
A DETECT 2-WIRE SMOKE Used for Class A, 2-wire detectors.
4-WIRE SMOKE Used for Class A, 4-wire detectors.
CO 4-WIRE DET Used for Class A, 4-wire CO detectors.
CO 4-WIRE SUP DET Latching or Non-latching used for Class A, 4-wire 
CO Supervisory detectors
Table 9.5  : Menu choices for Internal/External Power Module