EasyManua.ls Logo

Honeywell Silent Knight 6820EVS - 5865-3; 5865-4 LED Annunciator Installation; 1: 5865 Connection to Panel

Honeywell Silent Knight 6820EVS
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017 53
4.12 5865-3 / 5865-4 LED Annunciator Installation
The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote silence and reset key switches, and a general
system trouble LED. The 5865-3 has 30 mappable LEDs only. These are arranged as 15 pairs of red (typically used for alarm) and yel-
low (typically used for trouble) LEDs.
Installation of the 5865-5 and 5865-4 is identical. The key switches and the trouble LED follow the behavior of other system annuncia-
tors and do not require any installation steps. The following sub-sections describe how to install the 5865-3 and 5865-4 hardware. Refer
to Section 9 for programming information.
Figure 4.39 5865-3 and 5865-4 Assembly (front view)
4.12.1 5865 Connection to Panel
The 5865 connects to the panel via the SBUS. Make connections as shown in Figure 4.40. After the 5865 is connected to the panel, it
must be added to the system. This programming step is described in Section 4.13.
Figure 4.40 5865 Connection to the FACP
NOTE: This manual uses “5865” when referring to aspects of the 5865-3 and 5865-4 that are common to both models.