6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017 25
3.7.3 Current Draw Worksheet for SD SLC Devices
Use Table 3.3 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. You can
install up to 127 SD devices per loop.
5
Device # of Devices Current per Device
Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from battery) 1 Standby: 190 mA 190 mA
Alarm: 250 mA 250 mA
Addressable SLC Devices
SD500-AIM Standby/Alarm: .55 mA
1
mA mA
SD500-MIM mA mA
SD500-PS mA mA
SD500-ARM mA mA
SD505-HEAT mA mA
SD505-PHOTO mA mA
SD500-ANM Aux. Pwr Standby: 8 mA mA
Alarm: 60 mA mA
SLC Standby/Alarm: .55 mA mA mA
SD500-SDM SLC Standby/Alarm: .55 mA mA
Aux. Pwr Standby: 20 mA mA
Alarm: 106 mA mA
SLC Accessory Bases
SD505-6RB Standby/Alram: .082 mA mA mA
SD505-6SB Aux. Pwr Standby: 1 mA mA
Alarm: 32 mA mA
SLC Standby/Alarm .082 mA mA mA
SD505-DUCTR Aux. Pwr Standby: 20 mA
2
mA
Alarm: 62 mA
2
mA
SLC Standby/Alarm: .5 mA mA mA
SD505-DTS-K None, included with SD505-DUCTR worst case.
SD505-DUCT None, included with detector current.
SLC Isolator Devices
SD500-LIM (100 max/loop) Standby/Alarm .092 mA mA mA
SD505-6IB
Accessories Modules
5815XL SLC Loop Expander (63 max.) Standby/Alarm: 55 mA mA mA
6860 Remote LCD Annunciator. (16 max.) Standby: 25 mA mA
Alarm: 50 mA mA
5860 Remote LCD Annunciator. Standby: 20 mA mA
Alarm: 25 mA mA
6855 Remote LCD Annunciator Standby: 20 mA mA
Alarm: 25 mA mA
5824 Serial/Parallel Printer Interface (4 max.) Standby/Alarm: 45 mA mA mA
5895XL Power Supply (16 max.) Standby/Alarm: 10 mA mA mA
5496 NAC Expander Standby/Alarm: 10 mA mA mA
5865-4 LED Annunciator Module
(with reset and silence switches)
(8 max.) Standby: 35 mA mA
Alarm: 145 mA mA
5865-3 LED Annunciator Module Standby: 35 mA mA
Alarm: 145 mA mA
5880 LED I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
5883 Relay Interface (32 max.) Standby: 0 mA mA
Alarm: 220 mA
(22 mA per relay)
mA
Table 3.3 Current Draw Worksheet for SD SLC Devices