176 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
3. Press the up or down arrow to toggle NO to YES then press ENTER.
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4. Select the SLC loop.
5. Enter the SLC address of the device you wish to locate.
The LED on the selected device will start flashing.
6. Press the left arrow to exit the SLC Device Locator.
13.4.2 SLC Multiple Locator
This feature is the same as SLC Device Locator, except you can locate up to 8 devices on a single search.
Follow these instructions to locate multiple SLC devices:
1. Select 2 (Point Functions) from the Main Menu.
2. Select 5 (SLC Multiple Device Locator).
A message similar to the one shown in Figure 13.2 will display.
Figure 13.2 Shut Down Warning
3. Press the up or down arrow to toggle NO to YES then press ENTER.
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4. Select the SLC loop.
5. Enter up to 8 SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6. Press the left arrow to exit SLC Multiple Device Locator.
13.4.3 I/O Point Control
This feature allows you to toggle any output on or off and trip any input device. This can be useful to test a point’s output mapping.
Follow these steps to control a I/O point:
1. Select 2 for Point Functions from the Main Menu.
2. Select 6 for I/O Point Control.
3. Select the module the point is on.
4. Use the up or down arrow to select the point you wish to test.
5. Press ENTER to generate an alarm for an input point or activate an output point.
6. To exit press the left arrow.
NOTE: Once you exit, the system will resume normal operation.