24 6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
1. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
2. The SK-DUCT housing contains a vacant mount for a SK-RELAY (sold separately). Current draw for the SK-RELAY is
calculated by increasing the SK-RELAY row of the calculation sheet by one for each SK-RELAY used with a SK-DUCT.
3. SK-BEAM-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be considered
when determining auxiliary power capacity but not calculated into current requirements for day to day operation.
4. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed
during that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current
that can be drawn from the panel.
5. Use next size battery with capacity greater than required.
6. Total does not include isolator devices or accessory bases.
EVS-LOC Local Operating Console
(includes 6860, RVM & SW-24)
(4 max.) Standby: 100mA mA
Alarm: 150mA mA
EVS-100W 100W amplifier (4 max.) Standby/Alarm: 10mA mA mA
EVS-100WBU backup daughter card (4 max.) Standby/Alarm: 10mA mA mA
Total System Current
Network Cards
SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21mA mA mA
SK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53mA mA mA
SK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79mA mA mA
Wireless Modules
WSK-WGI Wireless Gateway
Max current using ext supply 40mA mA mA
Max current SLC Power 24mA mA mA
Auxiliary Devices
4
Refer to devices manual for current rating.
IPDACT-2 IP Communicator
(1 max.) Standby: 93mA mA
Alarm: 136mA mA
IPDACT-2UD IP Communicator
(1 max.) Standby: 98mA mA
Alarm: 155mA mA
CELL-MOD/CELL-CAB-SK
Standby: 55mA mA
Alarm: 100mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
5495/5499 Power Supply
24 VDC One input circuit: 15mA
mA
Both input circuits: 30mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Notification Appliances Current
mA
Total current ratings of all devices in system (line A + line B + C) mA mA
Total current ratings converted to amperes (line D x .001): A A
Number of standby hours: H
Multiply lines E and F. Total standby AH AH
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H
Multiply lines E and H. Total alarm AH
AH
Add lines G and I.
5
AH
Multiply by the Derating Factor x 1.25
Total ampere hours
required
Device # of Devices Current per Device
Standby
Current
Alarm
Current
Table 3.2 Current Draw Worksheet for SK SLC Devices