6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017 111
Point
(cont.)
Internal Power
and External
Power
Enter Pt /Select Function
(cont.)
Select
Sensor
EVS TAMPER Latch and Non-Latch feature
only appear for
WATERFLOW,FIRE
SUPERVISORY, FIRE
TAMPER, ZONE AUX1, ZONE
AUX2, SYSTEM AUX1,
SYSTEM AUX2., EVS INPUT,
EVS TAMPER, and EVS
SUPERVISORY
EVS SUPER-
VISORY
STATUS
POINT
A SWITCH Same as B SWITCH
B
DETECT
2-WIRE SMOKE
4-WIRE SMOKE
CO 4 WIRE DET
A
DETECT
2-WIRE SMOKE
4-WIRE SMOKE
CO 4 WIRE DET
Select Group or Zone
Number
Group or Zone selection will
appear depending on the
function selected
Edit Name Enter Name
5880/5865/EVS-
Series Amplifiers
Enter Point #
UNUSED
Section 9.5.4
NOTIF
Select Group
Edit Name Enter Name
System
Options
Communication
Options
Auto Time Test
Set the Hour
*02:00AM
Section Auto Test Time
Set the Minutes
Select AM/PM
Enter Interval
24 hrs,12 hrs,
*6 hrs, 4 hrs
Phone Lines
For each phone line (1 & 2) select:
Section Phone
Lines
Dialing Prefix Up to 9 digits *none
# of Answer Rings Range: 00-15 *06
Select Dialing Option
TT *TT
TT/PL
PULSE
Rotary Pulse Format
U = 60/40 *U
E = 66/34
Dial Tone Disabled
Y or N *N
Monitor Line
Y or N *N
Answering Machine
Bypass
Y or N
*N
Phone Line Unused
Y or N *N
Menu Options/Defaults Comments
Table 8.2 Programming Quick Reference Table