6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017 121
SWITCH
(cont.)
P.A.S. ACK
Positive acknowledge switch. This switch must be used in zones
programmed as Positive Alarm Sequence (see , "Edit Zone
Properties").
If an acknowledge switch closes when an alarm or trouble condition
is not already in progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type.
The switch must be rated at 5V, 100 mA (minimum) and be used
with an EOL resistor for supervision.
ZONE AUX1
Latching
Use these switch types if you want to monitor special zone-level
conditions (such as dry contact from a remote power supply).
Non Latching
ZONE AUX2
Latching
Non Latching
SYSTEM AUX1
Latching
Use these switch types if you want to monitor special system-wide
conditions (such as dry contact from a remote power supply).
Non Latching
SYSTEM AUX2
Latching
Non Latching
DETECTOR
Used to monitor conventional 4-wire detectors, a contact closure will
generate a detector alarm event.
FIRE TAMPER
Latching
Performs identically to a supervisory switch, but will be indicated as
a tamper switch on the LCD annunciator.
Non Latching
MANUAL
RELEASE
Manual release switch
INTERLOCK Interlock release switch input.
STATUS POINT
EVS INPUT
Latching
User also has EVS Event Number 1-8 option for EVS INPUT.
Only available when an EVS-VCM is installed in the system.
Non Latching
EVS TAMPER
Latching
Non Latching
EVS SUPER-
VISORY
Latching
Non Latching
CO DETECT SW CO Detector Switch
CO
SUPERVISORY
DETECT SW
CO Supervisory Detector Switch
NOTIF
OUTPUT PT Select Group
Output point, a general use notification type. Use for driving
standard notification appliances.
AUX CONST
Use constant power for applications that require a constant auxiliary
power source. Power is always present at constant circuits.
AUX RESET
Use for auxiliary power, resettable applications. See Section 4.16.3
for a description of how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section 4.16.3 for a description of how
this option operates.
RELAY
OUTPUT PT Select Group
Output point, a general use relay type. Use for applications requiring
a relay, such as fan shutdown, elevator recall, and so on.
AUX RESET
Use for auxiliary power, resettable applications. See Section 4.16.3
for a description of how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section 4.16.3 for a description of how
this option operates.
SLC LED
LED NUMBER 01-80 For use with SD devices only. 80 sub addresses on LED.
LED FUNCTION
Unused
NOTIF Notification can have group number.
Type Selection Function Latching Option Comments
Table 9.3 Programming Options for 5815XL Modules