6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017 165
EVS Supervisory/Tamper Alarm QS 0 QSNN000000 1 241 00 000
EVS Supervisory/Tamper Alarm
Restore
QR 0 QRNN000000 3 241 00 000
EVS Output Group Trouble QT Group #
+1000
QTNN001GGG 1 320 00 Group #
EVS Output Group Trouble
Restore
QJ Group #
+1000
QJNN001GGG 3 320 00 Group #
External Reset/Silence/Fire Drill
switch trouble
UT 0000 UTNN000000 1 373 00 000
External Reset/Silence/Fire Drill
switch trouble restore
UJ 0000 UJNN000000 3 373 00 000
LOC Mic Activated EVS Alarm QA 0 QANN000000 1 220 00 000
LOC Mic Activated EVS Alarm
Restore
QH 0 QHNN000000 3 220 00 000
LOC/Point EVS # Alarm QA Emergen-
cy #
QANN0E0000 1 220 +
Emer-
gency #
00 000
LOC/Point EVS # Alarm Restore QH Emergen-
cy #
QHNN0E0000 3 220 +
Emer-
gency #
00 000
Manual pull switch alarm FA Zone # FANN000ZZZ 1 115 00 Zone #
Manual pull switch alarm restore FH Zone # FHNN000ZZZ 3 115 00 Zone #
Manual pull switch trouble FT Zone # FTNN000ZZZ 1 373 00 Zone #
Manual pull switch trouble restore FJ Zone # FJNN000ZZZ 3 373 00 Zone #
Notification output trouble FT Group # +
1000
FTNN001GGG 1 320 00 Group #
Notification output trouble restore FJ Group # +
1000
FJNN001GGG 3 320 00 Group #
Positive Alarm Sequence ac-
knowledge switch trouble
FT Zone # FTNN000ZZZ 1 373 00 Zone #
Positive Alarm Sequence ac-
knowledge switch trouble restore
FJ Zone # FJNN000ZZZ 3 373 00 Zone #
SLC LED Module trouble ET 0000 ETNN000000 1 333 00 000
SLC LED Module trouble restore ER 0000 ERNN000000 3 333 00 000
Status Point Types Trouble UT 0 UTNN000000 1 379 00 000
Status Point Types Trouble
Restore
UJ 0 UJNN000000 3 379 00 000
Supervisory Detector Alarm FS Zone # FSNN000ZZZ 1 200 00 Zone #
Supervisory Detector Alarm
Restore
FR Zone # FRNN000ZZZ 3 200 00 Zone #
Supervisory/Tamper Alarm FS Zone # FSNN000ZZZ 1 200 00 Zone #
Supervisory/Tamper alarm condi-
tion restore
FR Zone # FRNN000ZZZ 3 200 00 Zone #
Supervisory/Tamper switch
trouble
FT Zone # FTNN000ZZZ 1 373 00 Zone #
Supervisory/Tamper switch
trouble restore
FJ Zone # FJNN000ZZZ 3 373 00 Zone #
System-based AUX1 switch
alarm
UA 1000 UANN001000 1 140 01 000
SIA Reporting Format Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 12.2 : Reporting Formats Table