6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017 167
Point Events
For SK devices, sensors 1–159 are reported as Points 1–159, modules 1–159 are reported
as Points 201–359.
An unexpected SLC device has
been detected
pi Exp. ID XE Point # XENNXXPPPP 1 380 Exp. ID Point #
An unexpected SLC device has
been removed
pi Exp. ID XI Point # XINNXXPPPP 3 380 Exp. ID Point #
Auxiliary power disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Auxiliary power enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Auxiliary power Trouble pi Exp. ID FT Point # FTNNXXPPPP 1 320 Exp. ID Point #
Auxiliary power trouble restore pi Exp. ID FJ Point # FJNNXXPPPP 3 320 Exp. ID Point #
Background Music Switch is
Trouble
pi Exp. ID UT Point # UTNNXXPPPP 1 379 Exp. ID Point #
Background Music Switch is
Trouble Restored
pi Exp. ID UJ Point # UJNNXXPPPP 3 379 Exp. ID Point #
Background Music Switch is
Disabled
pi Exp. ID UB Point # UBNNXXPPPP 1 580 Exp. ID Point #
Background Music Switch is
Enabled
pi Exp. ID UU Point # UUNNXXPPPP 3 580 Exp. ID Point #
CO Detector Trouble pi Exp. ID GT Point # GTNNXXPPPP 1 373 Exp. ID Point #
CO Detector Trouble Restore pi Exp. ID GJ Point # GJNNXXPPPP 3 373 Exp. ID Point #
CO Detector Disabled pi Exp. ID GB Point # GBNNXXPPPP 1 571 Exp. ID Point #
CO Detector Enabled pi Exp. ID GU Point # GUNNXXPPPP 3 571 Exp. ID Point #
Detector Alarm pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Detector Alarm restore pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Detector Disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Detector Enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Detector Trouble pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Detector Trouble restore pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Detector CO Alarm pi Exp. ID GA Point # GANNXXPPPP 1 162 Exp. ID Point #
Detector CO Alarm Restore pi Exp. ID GH Point # GHNNXXPPPP 3 162 Exp. ID Point #
Detector CO Supervisory Alarm pi Exp. ID GS Point # GSNNXXPPPP 1 200 Exp. ID Point #
Detector CO Supervisory Alarm
Restore
pi Exp. ID GR Point # GRNNXXPPPP 3 200 Exp. ID Point #
EVS Alarm # Point Alarm pi Exp. ID QA (EPPP) E -
Emergen-
cy #
PPP -
Point #
QANNXXEPPP 1 220 +
Emer-
gency #
Exp. ID Point #
EVS Alarm # Point Alarm Restore pi Exp. ID QH (EPPP) E -
Emergen-
cy #
PPP -
Point #
QHNNXXEPPP 3 220 +
Emer-
gency #
Exp. ID Point #
EVS Alarm # Point Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 242 Exp. ID Point #
EVS Alarm # Point Trouble Re-
store
pi Exp. ID QJ Point # QJNNXXPPPP 3 242 Exp. ID Point #
EVS Alarm # Point Disabled pi Exp. ID QB Point # QBNNXXPPPP 1 243 Exp. ID Point #
EVS Alarm # Point Enabled pi Exp. ID QU Point # QUNNXXPPPP 3 243 Exp. ID Point #
SIA Reporting Format Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 12.2 : Reporting Formats Table