6820 / 6820EVS Manual P/N LS10144-001SK-E:C  09/28/2017 169
Manual pull switch alarm restore pi Exp. ID FH Point # FHNNXXPPPP 3 115 Exp. ID Point #
Manual pull switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Manual pull switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Manual pull switch trouble pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Manual pull switch trouble restore pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Manual release switch alarm 
(Water Release Zone)
pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Manual release switch alarm re-
store (Water Release Zone)
pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Manual release switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Manual release switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Manual release switch trouble 
(Water Release Zone)
pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Manual release switch trouble re-
store (Water Release Zone)
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Notification output point disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Notification output point enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Notification output point trouble pi Exp. ID FT Point # FTNNXXPPPP 1 320 Exp. ID Point #
Notification output point trouble 
restore
pi Exp. ID FJ Point # FJNNXXPPPP 3 320 Exp. ID Point #
Positive Alarm Sequence ac-
knowledge switch disabled
pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Positive Alarm Sequence ac-
knowledge switch enabled
pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Positive Alarm Sequence ac-
knowledge switch trouble
pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Positive Alarm Sequence ac-
knowledge switch trouble restore
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
Status Point Trouble pi Exp. ID UT Point # UTNNXXPPPP 1 379 Exp. ID Point #
Status Point Trouble Restored pi Exp. ID UJ Point # UJNNXXPPPP 3 379 Exp. ID Point #
Status Point is Disabled pi Exp. ID UB Point # UBNNXXPPPP 1 580 Exp. ID Point #
Status Point is Enabled pi Exp. ID UU Point # UUNNXXPPPP 3 580 Exp. ID Point #
Supervisory/Tamper Alarm  pi Exp. ID FS Point # FSNNXXPPPP 1 200 Exp. ID Point #
Supervisory/Tamper Alarm 
Restore
pi Exp. ID FR Point # FRNNXXPPPP 3 200 Exp. ID Point #
Supervisory/Tamper point dis-
abled
pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Supervisory/Tamper point en-
abled
pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Supervisory/Tamper point trouble pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Supervisory/Tamper point trouble 
restore
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
System-based AUX1 switch 
alarm
pi Exp. ID UA Point # UANNXXPPPP 1 140 Exp. ID Point #
System-based AUX1 switch 
alarm restore
pi Exp. ID UH Point # UHNNXXPPPP 3 140 Exp. ID Point #
System-based AUX1 switch dis-
abled
pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
SIA Reporting Format Contact ID Reporting Format
SIA pi Modifier  SIA
Event Description Module 
ID # (If 
Any)
SIA 
Event 
Codes
Parameter Fixed Length 
Format NN - 
panel ID 
XX- SBUS ID 
ZZZ- Zone #   
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event 
Code
Group # Contact #
Table 12.2  : Reporting Formats Table