Ground Bonding kit 59
Installing the ground bonding rack option kit on HP 10000 G2
Series Rack 150-mm extension kits
1. Insert a T-25 Torx screw through one end of a 15.24-cm (6-in) grounding strap, and secure it to the rear
rack chassis.
2. Place an M8 internal serrated lock washer and the other end of the same grounding strap over the
grounding lug on the extension kit.
3. Place an M8 hex nut over the grounding lug and tighten.
Installing the ground bonding rack option kit on HP 10000 G2
Series Rack 200-mm extension kits
From the extension kit to the bottom rack side panel:
1. Insert a T-25 Torx screw through the end of the 36.83-cm (14.5 in) grounding strap, and secure it to the
bottom side panel.
2. Place the other end of the same grounding strap over the grounding lug on the extension kit.