Hardware options installation 55
17.
Install the fan cage. The fan cage should be populated with high-performance fans when installing
the Express Bay Enablement option.
18. Install the air baffle (on page 33).
19. Install the access panel (on page 28).
20. Do one of the following:
o Slide the server into the rack.
o Install the server into the rack.
21. Connect each power cord to the server.
22. Connect each power cord to the power source.
23. Power up the server ("Powering up the server" on page 26).
Redundant hot-plug power supply option
CAUTION: All power supplies installed in the server must have the same output power
capacity. Verify that all power supplies have the same part number and label color. The system
becomes unstable and may shut down when it detects mismatched power supplies.
CAUTION: To prevent improper cooling and thermal damage, do not operate the server
unless all bays are populated with either a component or a blank.
To install the component:
1. Access the product rear panel (on page 28).
2. Remove the blank.
WARNING:
To reduce the risk of personal injury from hot surfaces, allow the power supply or
power supply blank to cool before touching it.