3
Table 2 Dust concentration limit in the equipment room
Substance Concentration limit (particles/m³)
Dust
3 × 10
4
(no visible dust on the tabletop over three days)
NOTE:
Dust diameter 5 μm
The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion
and premature aging of components, as shown in Tabl e 3 .
Table 3
Harmful gas limits in the equipment room
Gas Maximum concentration (mg/m
3
)
SO
2
0.2
H
2
S 0.006
NH
3
0.05
Cl
2
0.01
EMI
All electromagnetic interference (EMI) sources, from outside or inside of the switch and application
system, adversely affect the switch in the following ways:
A conduction pattern of capacitance coupling.
Inductance coupling.
Electromagnetic wave radiation.
Common impedance (including the grounding system) coupling.
To prevent EMI, use the following guidelines:
If AC power is used, use a single-phase three-wire power receptacle with protection earth (PE)
to filter interference from the power grid.
Keep the switch far away from radio transmitting stations, radar stations, and high-frequency
devices.
Use electromagnetic shielding, for example, shielded interface cables, when necessary.
To prevent signal ports from getting damaged by overvoltage or overcurrent caused by lightning
strikes, route interface cables only indoors.
Laser safety
WARNING!
Do not stare into any fiber port when the switch has power. The laser light emitted from the optical
fiber might hurt your eyes.
The HPE FlexFabric 5710 switches are Class 1 laser devices.
Installation tools
No installation tools are provided with the switch. Prepare the following tools yourself:

Table of Contents

Other manuals for HPE FlexFabric 5710 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HPE FlexFabric 5710 Series and is the answer not in the manual?

HPE FlexFabric 5710 Series Specifications

General IconGeneral
ModelHPE FlexFabric 5710 Series
Power SupplyAC or DC
Operating Temperature0°C to 45°C
Routing ProtocolOSPF, BGP, RIP
Input Voltage100-240V AC
Operating Humidity10% to 90% (non-condensing)
Jumbo Frame SupportUp to 9216 bytes
ManagementCLI, SNMP