Item Specifications
Packing materials:
l Chassis packing materials: 30 kg (66.15 lb)
l Half-width node packing materials: 2.3 kg (5.07 lb)
l Full-width node packing materials: 3.6 kg (7.94 lb)
Floor bearing capacity The weight of a cabinet without a chassis is about 200 kg
(441.00 lb). A cabinet occupies an area of about 1.44 m
2
(15.50 ft.
2
). The following lists the requirements for the floor
bearing capacity based on the number of E9000 chassis in a
cabinet:
l One E9000 chassis: 347.2 kg/m
2
(0.49 bf/in.
2
)
l Two E9000 chassis: 555.5 kg/m
2
(0.79 bf/in.
2
)
l Three E9000 chassis: 763.9 kg/m
2
(1.09 bf/in.
2
)
Table 2-17 Environmental specifications
Item
Specifications
Temperature Server:
l Operating temperature: 5°C to 40°C (41°F to 104°F)
(ASHRAE Class A3 compliant)
l Storage temperature: –40°C to +65°C (–40°F to +149°F)
l Temperature change rate: < 20°C/h (36°F/h)
PSU:
l Operating temperature: –5°C to +50°C (23°F to 122°F)
l Storage temperature: –40°C to +85°C (–40°F to +185°F)
Fan module:
l Operating temperature: –10°C to +70°C (14°F to 158°F)
l Storage temperature: –40°C to +75°C (–40°F to +167°F)
Humidity
l Operating humidity: 5% RH to 85% RH (non-condensing)
l Storage humidity: 5% RH to 95% RH (non-condensing)
l Humidity change rate: < 20% RH/h
E9000 Server
User Guide
2 Overview
Issue 25 (2019-11-30) Copyright © Huawei Technologies Co., Ltd. 41