Figure 6-2 Installing pipes
(1) Water rell pipe (2) Drainpipe
1. Remove the tinfoil on the plug of the water rell valve.
2. Connect the PP-R pipe connector to the pipes on both ends using a hot melt
device.
3. Install the other pipes in the same way.
Step 4 After the hot-melt connection, wrap the exposed part of the water pipe with 10
mm thick thermal insulation foam.
----End
Follow-up Procedure
Verify that the pipe connector is closely melted with the pipes at both ends.
FusionDC1000A Prefabricated All-in-One Data
Center
Installation Guide (IT Scenario)
6 Installing External Pipes for Smart Cooling
Products