● As the re cylinder is heavy, determine the installation position, port, and
fastening mode in advance to avoid long-distance movement.
● Do not impact or strike the re cylinder during transportation or installation.
Do not remove or ip the dowel on the re cylinder.
● Assign at least four persons for transportation and installation if no auxiliary
tool is available.
● After the 
re cylinder is installed, do not remove the safety pin on the re
cylinder. Instead, remove the safety pin only after the re extinguishing system
starts working properly.
● Do not touch any button in the 
re extinguishing system without permission
during installation.
● Do not power on the re extinguishing system during installation.
Preparations
Tools: at-head screwdriver, pallet truck, adjustable wrench, pipe wrench, step
ladder, protective gloves
Materials: 
re cylinder, high-pressure hose, sealing tape, threaded adapter, I-
shaped connector
Skill requirement: common technician
Procedure
Step 1 Move the re cylinder using a pallet truck to a position near the pre-fab. module
door closest to the installation position.
Do not move the re cylinder over a long distance by hands.
Step 2 Untie the precongured steel straps at the installation position of the re cylinder.
Step 3 Move the 
re cylinder to the installation position and secure it.
Keep the pressure gauge panel outwards so that people can view the reading,
which also facilitates later maintenance.
FusionDC1000A Prefabricated All-in-One Data
Center
Installation Guide (IT Scenario) 8 Installing Devices Inside the Pre-fab. Module
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 86