CA UTION
As the re cylinder is heavy, determine the installation position, port, and
fastening mode in advance to avoid long-distance movement.
Do not impact or strike the re cylinder during transportation or installation.
Do not remove or ip the dowel on the re cylinder.
Assign at least four persons for transportation and installation if no auxiliary
tool is available.
After the
re cylinder is installed, do not remove the safety pin on the re
cylinder. Instead, remove the safety pin only after the re extinguishing system
starts working properly.
Do not touch any button in the
re extinguishing system without permission
during installation.
Do not power on the re extinguishing system during installation.
Preparations
Tools: at-head screwdriver, pallet truck, adjustable wrench, pipe wrench, step
ladder, protective gloves
Materials:
re cylinder, high-pressure hose, sealing tape, threaded adapter, I-
shaped connector
Skill requirement: common technician
Procedure
Step 1 Move the re cylinder using a pallet truck to a position near the pre-fab. module
door closest to the installation position.
NO TICE
Do not move the re cylinder over a long distance by hands.
Step 2 Untie the precongured steel straps at the installation position of the re cylinder.
Step 3 Move the
re cylinder to the installation position and secure it.
NO TICE
Keep the pressure gauge panel outwards so that people can view the reading,
which also facilitates later maintenance.
FusionDC1000A Prefabricated All-in-One Data
Center
Installation Guide (IT Scenario) 8 Installing Devices Inside the Pre-fab. Module
Issue 01 (2021-04-20) Copyright © Huawei Technologies Co., Ltd. 86