Table 12-12 Setting parameters for the reused DG
Main Menu Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default
Value
Setting
Parameters
Settings
Genset Genset 1 Rated Power 12.5 kW Set this
parameter as
required.
NOTE
● The peak
shaving
function
and AC
power
limiting
can be
enabled
only when
the AC
input
capacity is
greater
than the
capacity of
the power
subrack.
● When the
AC input
capacity is
less than
the
capacity of
the power
subrack,
do not
enable the
peak
shaving
function or
AC power
limiting.
Power Limit
Rate
80.0% Set this
parameter as
required.
Genset Work
Cond.
Close Set this
parameter as
required.
Output OV
Thres.
120.0% Set this
parameter as
required.
Output UV
Thres.
80.0% Set this
parameter as
required.
PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide 12 Power-on and Commissioning