Main Menu Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default
Value
Setting
Output Mode 3-Phase 4-
Wire
Set this
parameter as
required.
Rated Phase
Volt
230 V Set this
parameter as
required.
Rated
Frequency
50 Hz Set this
parameter as
required.
Output Over
Freq
110.0% Set this
parameter as
required.
Output Under
Freq
94.0% Set this
parameter as
required.
Runtime
Maint.
9999h Set this
parameter as
required.
Scheduled
Maint.
500h Set this
parameter as
required.
Step 2 Set monitoring parameters for the reused DG.
Table 12-13 Setting parameters for the reused DG
Main Menu
Second-Level
Menu
Third-Level
Menu
Fourth-Level
Menu
Default
Value
Setting
Parameters
Settings
Other Device
Cong
Fuel Tank 1 Tank Type Vertical
Cylinder
Set based on
site
requirements.
Colum Tank
Diameter
NOTE
This
parameter is
displayed
when Tank
Type is set to
Vertical
Cylinder or
Horizontal
Cylinder.
1.13m Set the
parameters
based on the
actual
diameter.
PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide 12 Power-on and Commissioning
Issue 02 (2021-09-28) Copyright © Huawei Technologies Co., Ltd. 130