Figure 5-41 Installing battery communications cables (6+6 and 6+0 scenarios)
Figure 5-42 Securing battery communications cables
Step 5 Install battery copper bars and power cables.
1. Open the protective covers for the negative terminal of the battery module on
the upper layer and the positive terminal of the battery module on the lower
layer.
2. Install copper bars between battery modules. Install the copper bar end with
a round hole at the battery module on the upper layer, and close the terminal
protective cover. Install the copper bar end with a slotted hole at the battery
module on the lower layer, and close the terminal protective cover.
3. Repeat these two steps.
4. Open the terminal protective covers, install the battery power cables reserved
in the cabinet, and close the terminal protective covers.