EasyManuals Logo

iDect FC6A series User Manual

iDect FC6A series
474 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #147 background imageLoading...
Page #147 background image
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722 3-17
3: I
NSTALLATION
AND
W
IRING
Power Supply and Power Supply Wiring
Power Supply
This section describes how to connect a power supply to the FC6A Series MicroSmart.
All-in-One Type
There are three power supply specifications for the All-in-One Type: the AC power type, the 24V DC power type, and the 12V DC
power supply type.
â–  When Power Is Turned Off
• The power supply voltages that can be used with the All-in-One Type are as follows.
AC power type: 85 to 264V AC
24V DC power type: 20.4 to 28.8V DC
12V DC power type: 10.2 to 18.0V DC
• The power failure detection voltage varies depending on the usage conditions of the inputs and outputs, but a power failure is
normally detected when the power supply voltage is the following values.
AC power type: Less than 85V AC
24V DC power type: Less than 20.4V DC
12V DC power type: Less than 10.2V DC
• For all power supply types, a momentary power interruption of 10 ms or less is not recognized as a power failure when the
power voltage is at the rated voltage.
â–  Inrush Current at Powerup
The following inrush current flows through the FC6A Series MicroSmart when powered up. Use a power supply with sufficient
capacity.
AC power type: 40 A or lower
24V DC power type: 35 A or lower
12V DC power type: 35 A or lower
• Use a power supply of the rated value. Use of the wrong power supply may cause fire or malfunction.
• Ensure that the power voltage to the FC6A Series MicroSmart does not exceed the allowable power voltage range
described in the power supply specifications. The FC6A Series MicroSmart may run and stop repeatedly within this
voltage range, particularly if the power voltage turns on or off very slowly.
• Use an IEC 60127-approved fuse on the power line outside the FC6A Series MicroSmart. This is required when equipment
containing the FC6A Series MicroSmart is destined for Europe.
Caution
All-in-One Type
-
+
External Power Supply
12V DC
-
+
External Power Supply
24V DC
AC Power Type
24V DC Power Type 12V DC Power Type
AC Power Input
L N PE
12V DC Power Input
+12 V
-
FE
24V DC Power Input
+24 V
-
FE
Do not use the FC6A Series MicroSmart outside of the power supply voltages listed above.
When an external device that carries the risk of causing a serious accident is connected to the inputs and outputs of the
FC6A Series MicroSmart, implement measures in the external circuit (such as voltage monitoring) so that the device will
function safely when there is a failure.
Warning

Table of Contents