Input/Output Wiring
This section describes FC6A Series MicroSmart input/output device wiring.
Precautions for I/O Device Wiring
Input Terminal Wiring
When wiring input devices, separate wiring from power, output, and motor lines.
For the wires to use with the PU modules, expansion modules, and option modules, see "Recommended Ferrule List" on page 3-
35.
Output Terminal Wiring
DC Sink Input Wiring Example DC Source Input Wiring Example
DC.IN
0
4
5
6
7
1
2
3
FC6A-N08B1
COM COM COM 7 6 5 4 3 2 1 0
+
-
-
+
PNP
2-wire
Sensor
24V DC
DC.IN
0
4
5
6
7
1
2
3
FC6A-N08B1
COM COM COM 7 6 5 4 3 2 1 0
-
+
+
-
NPN
2-wire
Sensor
24V DC
If output relays or transistors in the FC6A Series MicroSmart or output modules should fail, outputs may remain on or off.
For output signals which may cause heavy accidents, provide a monitor circuit outside the FC6A Series MicroSmart.
Connect a fuse to the output module, selecting a fuse appropriate for the load.
When equipment containing the FC6A Series MicroSmart is intended for use in European countries, insert an IEC 60127-
approved fuse to each output of every module for protection against overload or short-circuit. This is required when
equipment containing the FC6A Series MicroSmart is destined for Europe.
When driving an inductive load that emits noise like a magnet or a valve, to reduce noise and protect circuits, use a diode
for the output on DC power type models and a surge absorber for the output on AC power type models.
For the wires to use with the CPU modules, expansion modules, and option modules, see "Recommended Ferrule List" on
page 3-35.