FC9Y-B1722 10-1
10: ANALOG CARTRIDGE
This chapter provides an overview of the analog cartridges, their specifications, and also describes analog parameter settings and
configuration methods.
Analog Cartridge Overview
This section provides an overview of the analog cartridges and describes the compatible cartridge slots.
Analog cartridges are used to expand the analog inputs or analog outputs. They are available in the analog input type and the
analog output type. The analog input type is called the analog input cartridge, and the analog output type is called the analog
output cartridge. The analog data and analog status of the analog cartridge is stored in special data registers. For details, see "(5)
Data" on page 10-6.
To use an analog cartridge, it must be configured in the Module Configuration Editor. For detailed configuration methods, see
"Expansion Module and Cartridge Settings" on page 12-1. For details on the analog parameter settings, see "Analog Parameter
Settings" on page 10-4.
Cartridge Slots
The CPU module is equipped with a maximum of two cartridge slots that are used to install the analog cartridges. The FC6A Series
MicroSmart can be expanded with a maximum of four analog inputs or analog outputs by installing a maximum of two analog
cartridges.
Furthermore, the FC6A Series MicroSmart can be expanded with a maximum of two analog inputs or analog outputs by connecting
the HMI module to the left side of the CPU module and installing an analog cartridge.
For example, when the HMI module is connected to the 40-I/O type, the FC6A Series MicroSmart can be expanded with a
maximum of six analog inputs or analog outputs by installing a maximum of three analog cartridges.
Select the analog cartridges for the connected devices and configure the signal type.
CPU Module HMI Module
Cartridge Slot 1 Cartridge Slot 2 Cartridge Slot 3
All-in-One Type
16-I/O type Yes ― Yes
24-I/O type Yes ― Yes
40-I/O type Yes Yes Yes
CAN J1939 All-in-One Type Yes Yes Yes
Cartridge Slot 1
Cartridge Slot 2
Cartridge Slot 3
• Always install or remove the analog cartridges in the FC6A Series MicroSmart when the power is turned off. If an
analog cartridge is installed or removed in the FC6A Series MicroSmart when the power is on, the product may be
damaged. There is also a risk that the analog cartridge may not operate correctly.
• The analog cartridge may be damaged when dropped, so take great care not to drop it when removing it.
• Correctly install the analog cartridges in the analog cartridge slots.
• For details on how to install and remove the analog cartridge, see "Assembling the CPU Module and a Cartridge" on
page 3-6 and "Assembling the HMI Module and a Cartridge" on page 3-7.
Caution

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the iDect FC6A series and is the answer not in the manual?

iDect FC6A series Specifications

General IconGeneral
BrandiDect
ModelFC6A series
CategoryController
LanguageEnglish