6: D
EVICES
6-26 FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
S
M
ANUAL
FC9Y-B1722
D8250: Read SD Memory Card Capacity
This register indicates the capacity of the recognized SD or SDHC (maximum size 32 GB) memory card in megabytes.
It is 0 when no SD memory card has been inserted or if it is not recognized.
D8251: Read SD Memory Card Free Capacity
This register indicates the free capacity of the SD memory card in megabytes.
It is 0 when no SD memory card has been inserted or if it is not recognized.
D8254: SD Memory Card Download/Upload Execution Information
Information about the SD memory card download/upload that was executed.
For details, see "SD Memory Card" on page 11-1.
D8255: SD Memory Card Download/Upload Execution Status
The status of the SD memory card download/upload that was executed.
For details, see "SD Memory Card" on page 11-1.
D8260: Recipe Block Number
The recipe block number to read or write using special internal relays.
All channels for the specified block number are applicable.
D8261: Recipe Execution Block Number
The recipe block number of the recipe that was executed.
This is updated when the recipe block starts, and the status is retained when completed.
D8262: Recipe Execution Channel No.
The channel number of the recipe that was executed.
This is updated when the channel processing starts, and the status is retained when completed.
D8263: Recipe Execution Operation
Information about the operation of the recipe that was executed.
For details on recipes, see "Recipe Function" on page 11-7.
D8264: Recipe Execution Status
The status of the recipe that was executed.
For details on recipes, see "Recipe Function" on page 11-7.
D8265: Recipe Execution Error Information
Error information about the recipe that was executed.
For details on recipes, see "Recipe Function" on page 11-7.
D8278, D8279: Communication Mode Information (Client Connection) (Connection 1 to 8)
D8278 = Indicates the communication mode of connections 1 through 4.
D8279 = Indicates the communication mode of connections 5 through 8.
The allocation of connections in the device (bit assignment) is as follows.
Client connection (most significant bit = 0)
0000: Unused
0001: User Communication
0010: Modbus TCP client
Bit
15
Bit
0
Bit
7
Bit
8
Connection 1
Connection 2
Connection 3
Connection 4
D8278
Bit
15
Bit
0
Bit
7
Bit
8
Connection 5
Connection 6
Connection 7
Connection 8
D8279