2: P
RODUCT
S
PECIFICATIONS
2-22 FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
S
M
ANUAL
FC9Y-B1722
12V DC Power Type
Output Internal Circuit
Type No. FC6A-C40K1DE FC6A-C40K1DEJ
No. of Outputs 16
Output Points
per Common
Line
COM0 8
COM1 8
Rated Load Voltage 12V DC
Operating Load Voltage Range 10.2 to 18.0V DC 10.2 to 16.0V DC
Terminal Arrangement See "12V DC Power Type" on page 2-34
Maximum Load
Current
1 0.5 A maximum
1 Common 4 A maximum
Voltage Drop (ON Voltage) 1 V or less, voltage between COM and output terminal when ON
Maximum Inrush Current 1 A
Leakage Current 0.1 mA maximum
Clamping Voltage 39 V±1 V 27 V±1 V
Maximum Lamp Load 12 W
Inductive Load L/R = 10 ms (18.0V DC, 1 Hz) L/R = 10 ms (16.0V DC, 1 Hz)
External Current Draw 100 mA maximum, 12V DC (+V terminal supply power)
Isolation
Between Output
Terminal and
Internal Circuit
Photocoupler isolated
Between Output
Terminals
Not isolated
I/O Terminal
Connector
Type See "12V DC Power Type" on page 2-34
Insertion/
Removal
Durability
100 times minimum
Output Delay
Turn ON Time
Q0 to Q1: 5 μs or less
Q2 to Q3: 30 μs or less
Q4 to Q7, Q10 to Q17: 300 μs or less
Q0 to Q7: 5 μs or less
Q10 to Q17: 300 μs or less
Turn OFF Time
Q0 to Q1: 5 μs or less
Q2 to Q3: 30 μs or less
Q4 to Q7, Q10 to Q17: 300 μs or less
Q0 to Q7: 5 μs or less
Q10 to Q17: 300 μs or less
V(+)
Output
COM(
-
)
Internal Circuit
T
2
T
1

Table of Contents