FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
S
M
ANUAL
FC9Y-B1722 2-67
2: P
RODUCT
S
PECIFICATIONS
*1 The total input delay time increases in proportion to the number of channels used. Input channels that have been set to unused are not
included in the number of enabled input channels.
*2 The arbitrary setting is a function that uses the digital resolution data by scaling it to arbitrary data (that arbitrarily sets the lower limit value and
the upper limit value). The range setting (-32,768 to 32,767) is specified with data registers.
Example: When -5 V is input, 1,024 is displayed as long as the arbitrary setting is not configured, but -500 is displayed when the arbitrary
setting is configured as upper limit value = 1,000 and lower limit value = -1,000, and this makes it easier to intuitively read the input
voltage value.
*3 Input data out of range is reflected in the status of the analog module.
Mixed Analog I/O Module
Effect of Improper Input Connection No damage
Maximum Permanent Allowed Overload
(No Damage)
13V DC, 40 mA or lower
Selection of Input Type and Input Range Using programming software
Calibration or Verification to Maintain Rated
Accuracy
Not possible
Type No. FC6A-L06A1 FC6A-L03CN1
Input Type
and
Input Range
Voltage
0 to 10 V
-10 to 10 V
Current
4 to 20 mA
0 to 20 mA
Thermocouple
(K) -200 to 1,300°C (-328 to 2,372°F)
(J) -200 to 1,000°C (-328 to 1,832°F)
(R) 0 to 1,760°C (32 to 3,200°F)
(S) 0 to 1,760°C (32 to 3,200°F)
(B) 0 to 1,820°C (32 to 3,308°F)
(E) -200 to 800°C (-328 to 1,472°F)
(T) -200 to 400°C (-328 to 752°F)
(N) -200 to 1,300°C (-328 to 2,372°F)
(C) 0 to 2,315°C (32 to 4,199°F)
Resistance Thermometer
Pt100: -200 to +850°C (-328 to 1,562°F)
Pt1000: -200 to +600°C (-328 to 1,112°F)
NI100: -60 to +180°C (-76 to 356°F)
NI1000: -60 to +180°C (-76 to 356°F)
Thermistor
Resistor
Input
Impedance
Voltage 1 M or higher
Current 50 or lower
Thermocouple 1 M or higher
Resistance Thermometer 1 M or higher
Thermistor 1 M or higher
Resistor 1 M or higher
AD
Conversion
Sample Duration Time 1 ms or 10 ms 10 ms, 100 ms, or 104 ms
Sample Repetition Time Sampling time × Number of enabled input channels
Total Input Delay Time
*1
Sample duration time + Sample repetition time + 1 scan time
Type of Input Single-ended
Operation Mode Self-scan
Conversion Method Σ∆ type ADC
Input Error
Maximum Error at 25°C ±0.2% of full scale ±0.1% of full scale
Temperature Coefficient 0.01%/°C 0.006%/°C
Type No. FC6A-J2C1
FC6A-J4A1 FC6A-J8A1
FC6A-J4CN1 FC6A-J8CU1
Lower Limit Value Upper Limit Value
0 4,095
When the digital resolution data is 12 bits