EasyManua.ls Logo

IFM AC1421 - Activate CODESYS PLC

IFM AC1421
131 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
49
ifm Programming Manual AS-i Gateway AC14 (4.2.x) 12/2017
Operation Transfer CODESYS project to device
>
8.1.1 Activate CODESYS PLC
17692
To enable the processing of the created PLC application, the device-internal CODESYS PLC must be
activated in the setup menu of AS-i Gateway AC14.
If the PLC application is to have a write access to the outputs of the AS-i slaves, the CODESYS PLC
must be activated additionally as controller instance of the AS-i slave outputs.
The following table shows the possible combinations of the parameters [Output access] and [Use PLC]
as well as the rights of the CODESYS PLC resulting thereof.
List
[Output access]
Checkbox
[Use PLC]
CODESYS PLC
Programmable
Access to
AS-i inputs
Access to
AS-i outputs
Gateway
no
yes
no
yes
yes
no
Manual
no
yes
no
yes
yes
no
PLC
*
yes
yes
yes
Legend:
* ...
Value fixed (greyed out)
To set the operating mode of the device:
1 Select menu page
>
Select [System settings] tab.
2 Set the controller instance of the outputs
Select the requested controller instance of the AS-i outputs in the [Output access] list.
Press [Accept selection] to activate the selection.
3 Activate CODESYS PLC
Activate [Use PLC] checkbox.
> CODESYS PLC is active.
4 Optional: Adjust device cycle
Select the requested device cycle time in the [Device cycle] list.
Press [Accept selection] to activate the selected value.

Table of Contents

Related product manuals