55
ifm Programming Manual AS-i Gateway AC14 (4.2.x) 12/2017
Operation Reset
>
8.3.2 Reset the application (warm)
13131
9069
To reset the application on the PLC, choose one of the following options:
CODESYS: command [Reset (warm)]
► In the device tree:
Highlight the required application as active application.
► Select [Online] > [Login] to establish a connection to the CODESYS PLC.
> CODESYS switches to online mode.
► Select [Online] > [Reset warm] to reset the application.
GUI: command [Reset]
► >
► Select [All Applications] tab.
► Use [Reset] to reset all applications.
GUI: command [Restart]
► >
► Select [System-reset] tab.
► Use [Restart] to reboot the device.
>
8.3.3 Reset the application (cold)
15687
To reset the application on the PLC, choose one of the following options:
Download the application to the device
► → Download the application to the device (→ p. 50)
CODESYS: command "Reset (cold)"
► In the device tree:
Highlight the required application as active application.
► Select [Online] > [Login] to establish a connection to the CODESYS PLC.
> CODESYS switches to online mode.
► Select [Online] > [Reset cold] to reset the application.
>
8.3.4 Reset the application (origin)
18962
To reset the application on the PLC:
CODESYS: command "Reset (origin)"
► In the device tree:
Highlight the required application as active application.
► Select [Online] > [Login] to establish a connection to the CODESYS-PLC.
> CODESYS switches to online mode.
► Select [Online] > [Reset origin] to reset the application.