p2 Section 4. Times. Version 1.01 CONCEPT IQ. Installation & Programming Manual.
TIMEZONES
TimeZones can be programmed to define a Start time and End time, and the Days of the Week on which the
TimeZone will be valid. TimeZone programming also provides a “Holiday” option to be enabled when assign-
ing the Days, to allow the TimeZone to still be valid on any dates defined as Holidays.
Once programmed, TimeZones can be used to arm & disarm Areas &/or control Auxiliary outputs automati-
cally.
START AND END TIMES
The Start and End Times are defined in 4 separate Addresses for each TimeZone.
TIMEZONE 1 START HOUR Default = 9
This Address defines the Hour component of the Start Time.
TIMEZONE 1 START MINUTE Default = 0
This Address defines the Minute component of the Start Time.
TIMEZONE 1 END HOUR Default = 17
This Address defines the Hour component of the End Time.
TIMEZONE 1 END MINUTE Default = 0
This Address defines the Minute component of the End Time.
TIMEZONE 1 DAYS OF THE WEEK Default = 2, 3, 4, 5, 6 Selected. (Mon - Fri)
Option : When Selected:
1 Sunday ¯|
2 Monday |
3 Tuesday | The TimeZone will be valid on the specified Day, or Days,
4 Wednesday | unless the date has been defined as a Holiday.
5 Thursday |
6 Friday |
7 Saturday _|
8 Holiday The TimeZone will always be valid on the Days of the Week selected above,
regardless of whether the date has been defined as a Holiday.
The default setting is 9:00 – 17:00 on all Weekdays (Working Hours)
TIMEZONE 2 (5 Addresses)
The default setting is 9:00 – 13:00 on Weekend Days (Overtime Hours)
TIMEZONE 3 (5 Addresses)
The default setting is 7:00 – 20:00 on every Day (Day-time)
TIMEZONE 4 (5 Addresses)
The default setting is 20:00 – 7:00 on every Day (Night-time)
Address
Data type:
Value
790
Range:
0 - 23
791
Range:
0 - 59
792
Range:
0 - 23
793
Range:
0 - 59
794
Data type:
Option
795
to
799
800
to
804
805
to
809

Table of Contents