p4 Section 10. Comms. Version 1.01 CONCEPT IQ. Installation & Programming Manual.
Test report minute
This Address sets the minute the test report will be sent.
e.g. If: The “Test Report period” option is set to 2,
the “Test Report Hour” is set to 22, and the “Test Report Minute” is set to 45.
Then a Test Report will be sent to the Central Station at 10:45 PM every Monday.
REMOTE CONNECT
These options allow the Installer to program various parameters relating to remote connection for Upload/
Download and/or DTMF Telephone remote control.
Remote connect options
This Address sets the remote connect method for programming the system with the Upload / Download
software. Remote connect for DTMF Telephone remote control is not affected by this setting.
Data: When selected:
0 Default. Remote connect not allowed
1 Remote connect enabled. (Without callback)
2 Remote connect enabled with Callback.
Rings to answer Default = 16 Rings.
This Address sets the number of rings before the system will answer an incoming call.
This setting is relevant to both Upload/Download connection and DTMF remote control connection.
Answering machine (Fax) bypass “Follow-on” time.
This feature is used when Upload/Download software or DTMF Telephone is trying to remotely connect to the
system, and an Answering Machine is connected to the same Telephone line. If this feature is enabled, the
remote device must call the system, then hang up within three rings. If the remote device calls the system
again within the programmed “Follow-on” time then the system will answer the call on the first ring & connect.
Data: When selected:
0 Default. Answering Machine Bypass disabled
1 Follow-on time = 10 secs
2 Follow-on time = 30 secs
3 Follow-on time = 60 secs
SERIAL PORT OPTIONS
Serial Port options allow the Installer to program the Communications Task and Baud rate for the Serial Port
on the Control Module.
Port 0 Communications Task
Data: When selected:
0 Default. Serial Port not used.
1 Securitel STU. (Not yet available)
2 Serial Printer. (Not yet available)
3 Upload / Download. (Requires the Serial Adapter Cable)
NOTE: While Upload/Download software is connected and communicating with the Control Module, DTMF
Remote Control is temporarily disabled.
53
Range:
0 -59 (min.)
Data type:
Value
54
Range:
0 -2
80
Range:
1 -16 (rings)
81
Range:
0 -3
Data type:
Value
82
Range:
0 -3