Function
code
Name LED display Set range
Minim-
um unit
Factory
default
value
Modication
description
F0-16
Carrier
frequency
adjustment
selection
Carrier
frequency
adjustment
selection
0: Fixed PWM, carrier frequency
temperature adjustment inactive
1: Random PWM, carrier
frequency temperature
adjustment inactive
2: Fixed PWM, carrier wave
temperature adjustment valid
3: Random PWM, carrier
frequency temperature
adjustment enabled
1 2
☆
F0-17
Speed-up
time 1
Speed-up time
1
0.0s
~
6500.0s 0.1s 20.0s
☆
F0-18
Speed-down
time 1
Speed-down
time 1
0.0s
~
6500.0s 0.1s 20.0s
☆
Group F1 Motor Parameters
F1-00
motor type
selection
motor type
selection
0: Common asynchronous motor
1: Variable frequency
asynchronous motor
2: Permanent magnetic
synchronous motor
1 0
★
F1-01 rated power rated power 0.4kW
~
1000.0kW 0.1kW
Model
dependent
★
F1-02 rated voltage rated voltage 0V
~
440V 1V 380V
★
F1-03 rated current rated current 0.01A
~
655.35A 0.01A
Model
dependent
★
F1-04
rated
frequency
rated
frequency
0.00 ~ maximum frequency 0.01Hz 50.00Hz
★
F1-05
rated rotation
speed
rated rotation
speed
0rpm
~
30000rpm 1rpm 1460rpm
★
F1-06
stator
resistance
stator
resistance
0.001Ω
~
65.535Ω 0.001Ω
Model
dependent
☆
F1-07
rotor
resistance
rotor
resistance
0.001Ω
~
65.535Ω 0.001Ω
Model
dependent
☆
F1-08
leakage
inductive
reactance
leakage
inductive
reactance
0.01mH
~
655.35mH 0.01mH
Model
dependent
☆
F1-09
mutual
inductive
reactance
mutual
inductive
reactance
0.1mH
~
6553.5mH 0.1mH
Model
dependent
☆
F1-10
no-load
current
no-load
current
0.01A
~
650.00A 0.01A
☆
F1-11
Tuning
selection
Tuning
selection
0: No operation
1: Static tuning
2: Complete tuning
1 0
★