Goodrive35 inverters Function codes
114
Detailed instruction of parameters
Setting range of P08.20:0~20000
Setting range of P08.21:0.0~100.0%
Integral
coefficient
of high
frequency
current
loop
High-frequ
ency
switching
point of the
current
loop
Inertia
identificatio
n torque
Because of the friction, it is necessary to set
identification torque for normal inertia identification.
0.0~100.0% (rated torque of the motor)
0: No operation
1: Starting identification: press “RUN” to enter into
the program after starting identification until display
“-END-”; the identified system inertia is saved in
P08.24.
The identified system inertia can be set manually
when the system inertia is known. The displayed
system inertia may be less than 0.001kgm
2
for the
motors below 1kW.
Setting range: 0.000~30.000 kgm
2
Identifying the system inertia correctly and enabling
the inertia compensation can improve the dynamic
response of the system.