Goodrive35 inverters Function codes
115
Detailed instruction of parameters
Ones: Enabling
0:Disabled
1:Enabled
Tens: Voltage selection
0: Internal setting
1:P8.27 setting
After the valid undervoltage stopping, the inverter
will decelerate to stop according to the time set by
P08.05.
Setting range: 250.0~1000.0V
Fault reset times: set the automatic fault reset times.
If the reset time exceeds this set value, the inverter
will stop to wait maintenance.
Interval time of automatic fault reset: the interval
between the time when the fault occurs and the time
when the reset action occurs.
Setting range of P08.28:0~10
Setting range of P08.29:0.1~3200.0s
Interval
time of
automatic
fault reset
Frequency
decreasing
ratio of the
dropping
control
The output frequency of the inverter changes as the
load. And it is mainly used to balance the power
when several inverters drive one load.
Setting range:0.00~50.00Hz
Goodrive35 supports the shift between two motors.
This function is used to select the shifting channel.
LED ones: shifting channel
0: terminal shifting; digital terminal is 35