When the output frequency exceeds the
corresponding frequency of FDT electrical level, the
multi-function digital output terminals will output the
signal of “frequency level detect FDT” until the output
frequency decreases to a value lower than (FDT
electrical level—FDT retention detection value) the
corresponding frequency, the signal is invalid. Below
is the ware form diagram:
Setting range of P08.32: 0.00Hz~P00.03
(the Max. frequency)
Setting range of P08.33: -200.0~100.0%
(FDT1 electrical level)
Setting range of P08.34: 0.00Hz~P00.03
(the Max. frequency)
Setting range of P08.35: -200.0~100.0%
(FDT2 electrical level)
When the output frequency is among the positive or
negative detection range of the set frequency, the
multi-function digital output terminal will output the
signal of “frequency arrival”, see the diagram below
for detailed information: