Goodrive35 inverters Function codes
116
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
1: MODBUS communication shifting
2: PROFIBUS/CANopen communication shifting
P08.32
FDT1
electrical
level
detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level, the
multi-function digital output terminals will output the
signal of frequency level detect FDT until the output
frequency decreases to a value lower than (FDT
electrical levelFDT retention detection value) the
corresponding frequency, the signal is invalid. Below
is the ware form diagram:
Setting range of P08.32: 0.00Hz~P00.03
(the Max. frequency)
Setting range of P08.33: -200.0~100.0%
(FDT1 electrical level)
Setting range of P08.34: 0.00Hz~P00.03
(the Max. frequency)
Setting range of P08.35: -200.0~100.0%
(FDT2 electrical level)
50.00
Hz
P08.33
FDT1
retention
detection
value
5.0%
P08.34
FDT2
electrical
level
detection
value
50.00
Hz
P08.35
FDT2
retention
detection
value
5.0%
P08.36
Frequency
arrival
detection
value
When the output frequency is among the positive or
negative detection range of the set frequency, the
multi-function digital output terminal will output the
signal of frequency arrival, see the diagram below
for detailed information:
0.00
Hz
www.barghmaher.ir