Goodrive35 inverters Function codes
117
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
The setting range:0.00Hz~P00.03
(the Max. frequency)
P08.37
Energy
braking
enable
This parameter is used to control the internal braking
pipe inside the inverter.
0:Disable
1:Enable
Note: Only applied to internal braking pipe.
1
P08.38
Threshold
voltage
After setting the original bus voltage to brake the
energy, adjust the voltage appropriately to brake
the load. The factory changes with the voltage
level.
The setting range:200.0~2000.0V
In order to prevent customers set the value is too
large, it is recommended setting range:
voltage
380V
660
range
685~750V
1080~1180V
380V
voltage:
700.0V
660V
voltage:
1120.0V
P08.39
Cooling
fan running
mode
0: Normal mode
1:The fan keeps running after power on
0
P08.40
PWM
selection
0x000~0x111
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
0x001