Loading...
Goodrive35 inverters Function codes
124
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
cycle. The longer the sapling cycle is, the slower the
response is.
Setting range: 0.001~1.000s
P09.08
PID control
deviation
limit
The output of PID system is the maximum deviation
relative to close loop reference. As shown in the
diagram below, PID adjustor stops to work during the
deviation limit. Set the function properly to adjust the
accuracy and stability of the system.
Setting range:0.0~100.0%
0.0%
P09.09
Output
upper limit
of PID
This parameter is used to set the upper and lower
limit of the PID adjustor output.
100.0 % corresponds to max. frequency or the max.
voltage of ( P04.31)
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
100.0
%
P09.10
Output
lower limit
of PID
-50.0
%
P09.11
Detection
value of
feedback
offline
Set the detection value of feedback offline, when the
feedback detection value is smaller than or equals to
the detected value, and the lasting time exceeds the
set value in P09.12, the inverter will report PID
feedback offline fault and the keypad will display
PIDE.
0.0%
P09.12
Detection
time of
feedback
offline
1.0s