Goodrive35 inverters Function codes
125
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
P09.13
PID
adjustment
0x000~0x111
LED ones:
0: Keep on integral adjustment when the frequency
achieves the upper and low limit; the integration
shows the change between the reference and the
feedback unless it reaches the internal integral limit.
When the trend between the reference and the
feedback changes, it needs more time to offset the
impact of continuous working and the integration will
change with the trend.
1: Stop integral adjustment when the frequency
achieves the upper and low limit. If the integration
keeps stable, and the trend between the reference
and the feedback changes, the integration will
change with the trend quickly.
LED tens: P00.08 is 0
0: The same with the setting direction; if the output of
PID adjustment is different from the current running
direction, the internal will output 0 forcedly.
1:Opposite to the setting direction
LED hundreds: P00.08 is 0
0: Limit to the maximum frequency
1: Limit to frequency A
0x001
P09.14
PID
0.0~200.0%
200.0